2 power connections, 1 mains connection, Installation – Lenze 8240 HVAC Series User Manual

Page 29

Advertising
background image

Installation

4-5

UOOuhäáã~_^NMMO

4.2.2

Power connections

4.2.2.1

Mains connection

Types 8221 to 8227

Types 8241 to 8246

PE

+UG

-UG

L1

L2

L3

hPRKMMVV

mb

iN

iO

iP

Jrd

Hrd

hPRKMNNO

Correct screen connection with screened cables:

D

Connect the screen with the conductive mounting plate

using a suitable clamp.

D

To improve the screen connection: Connect screen

additionally at the stud PE next to the power

connections.

Connect screen correctly
(required parts in the accessory kit):

D

Screw the screen plate

➀ onto the fixing brackets ➁.

D

Fix screen using cable lugs. Do not use the screen for

strain relief!

D

To improve the screen connection: Connect screen

additionally at the stud PE next to the power

connections.

cfd QJP

mêçéçë~д Сзк г~бел ЕзееЙЕнбзе UOOuLUOQu

D

`зееЙЕн нЬЙ г~бел Е~ДдЙл пбнЬ нЬЙ лЕкЙп нЙкгбе~дл iNI iOI iPK
J qáÖÜíÉåáåÖ нзкимЙл

Terminals

Type

L1, L2, L3, +UG, -UG

PE connection

8221 - 8223

4 Nm (35 lbin)

8224 - 8225

7 Nm (62 lbin)

8226 - 8227

12 Nm (106.2 lbin)

8241 - 8246

0.5 ... 0.6 Nm (4.4 ... 5.3 lbin)

3.4 Nm (30 lbin)