Configuration – Lenze 8240 HVAC Series User Manual

Page 74

Advertising
background image

Configuration

7-10

UOOuhäáã~_^NMMO

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Selection

Lenze

Name

C126* Selection of

communication

errors

-0-

-0-

No TRIP when stopping the communication

in the process channel

-1-

TRIP (-CEO-) when stopping the

communication in the process channel

Only for bus

operation

C127 Selection

Setpoint selection

-0-

-0-

Absolute setpoint selection in Hz via C046

or process channel

-1-

Standardized setpoint selection via C141

(0 ... 100 %) or process channel

(

± 16384 = f

dmax

(C011))

Only for bus

operation

C135* Control word

see Operating

Instructions 2102

C141* Standardized

setpoint

-100.00

{0.01 %}

100.00

Only for bus

operation
Only when C127 = 1

active

C142

¿ Start condition

-1-

-0-

Automatic start inhibited, flying-restart

circuit not active

-1-

Automatic start, if term. 28 HIGH,

flying-restart circuit not active

-2-

Automatic start inhibited, flying-restart

circuit active

-3-

Automatic start, if term. 28 HIGH,

flying-restart circuit active

C144

¿ Chopper-frequenc

y reduction

-1-

-0-

No chopper-frequency lowering

1

Automatic chopper frequency lowering

y reduction

-1-

Automatic chopper-frequency lowering

when

J

max

- 10

°C

C150* Status word

see Operating

Instructions 2102

C156* Current threshold

0

0

{1 %}

150

C161* Current fault

Only display

C162* Last fault

Only display

C163* Last but one fault

Only display

C164* Last but two fault

Only display

C170

¿ TRIP-reset

selection

-0-

TRIP-reset by pressing the STP key or LOW

signal at ctrl. enable

-1-

Auto-TRIP reset

C171 Delay for

Auto-TRIP-Reset

0.00

0.00

{0.01s}

60.00

C178* Operating time

Only display

C179* Mains switch-on

time

Only display

C181* Setpoint PID

controller

0.00

-480.00

{0.02 Hz}

480.00

Only when C181 ≠

0 active

C182* Integration time

ramp function

generator

S-shape

0.00

0.00

{0.01 s}

50.00

D

C182 = 0.00
- Linear ramp

function

generator

D

C182 > 0.00
- Ramp function

generator

S shape with

T

i

time = C182

C196*

¿ Input condition

autom. DC

injection brake

-0-

-0-

DC brake active at C050 < C019

-1-

DC brake active at C050 < C019

and

setpoint < C019

Show/Hide Bookmarks