Configuration – Lenze 8240 HVAC Series User Manual
Page 74
![background image](/manuals/566193/74/background.png)
Configuration
7-10
UOOuhäáã~_^NMMO
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C126* Selection of
communication
errors
-0-
-0-
No TRIP when stopping the communication
in the process channel
-1-
TRIP (-CEO-) when stopping the
communication in the process channel
Only for bus
operation
C127 Selection
Setpoint selection
-0-
-0-
Absolute setpoint selection in Hz via C046
or process channel
-1-
Standardized setpoint selection via C141
(0 ... 100 %) or process channel
(
± 16384 = f
dmax
(C011))
Only for bus
operation
C135* Control word
see Operating
Instructions 2102
C141* Standardized
setpoint
-100.00
{0.01 %}
100.00
Only for bus
operation
Only when C127 = 1
active
C142
¿ Start condition
-1-
-0-
Automatic start inhibited, flying-restart
circuit not active
-1-
Automatic start, if term. 28 HIGH,
flying-restart circuit not active
-2-
Automatic start inhibited, flying-restart
circuit active
-3-
Automatic start, if term. 28 HIGH,
flying-restart circuit active
C144
¿ Chopper-frequenc
y reduction
-1-
-0-
No chopper-frequency lowering
1
Automatic chopper frequency lowering
y reduction
-1-
Automatic chopper-frequency lowering
when
J
max
- 10
°C
C150* Status word
see Operating
Instructions 2102
C156* Current threshold
0
0
{1 %}
150
C161* Current fault
Only display
C162* Last fault
Only display
C163* Last but one fault
Only display
C164* Last but two fault
Only display
C170
¿ TRIP-reset
selection
-0-
TRIP-reset by pressing the STP key or LOW
signal at ctrl. enable
-1-
Auto-TRIP reset
C171 Delay for
Auto-TRIP-Reset
0.00
0.00
{0.01s}
60.00
C178* Operating time
Only display
C179* Mains switch-on
time
Only display
C181* Setpoint PID
controller
0.00
-480.00
{0.02 Hz}
480.00
Only when C181 ≠
0 active
C182* Integration time
ramp function
generator
S-shape
0.00
0.00
{0.01 s}
50.00
D
C182 = 0.00
- Linear ramp
function
generator
D
C182 > 0.00
- Ramp function
generator
S shape with
T
i
time = C182
C196*
¿ Input condition
autom. DC
injection brake
-0-
-0-
DC brake active at C050 < C019
-1-
DC brake active at C050 < C019
and
setpoint < C019