Commissioning

5-12

UOOuhäáã~_^NMMO

5.5.1

Standardisation of process value

UONuLUOOu лЙннбеЦ к~åÖÉLUOQuW

Code

Name

Possible settings

IMPORTANT

Lenze Selection

Info

C500* Display factor

application datum

2000 1

{1}

25000

application datum

numerator

C501* Display factor for

process variable

10

1

{1}

25000

process variable

denominator

Function

Adaption of the field-frequency related parameters C010, C011, C017, C019, C037, C038, C039,

C050,C051 and C181 to a process value to be controlled, e.g. pressure, temperature, flow rate,

humidity or speed. By this, an absolute or relative display or selection of a process value can be

implemented.

Adjustment

The display value CXXX is calculated from:

CXXX =

C011

200

C500
C501

Example

Relative or absolute selection and display of a speed setpoint

P

soll

= 5 bar, fdmax =50Hz:

a) Relative standardisation in %

100, 0 (%) =

50

200

4000

10

(e. g. C500=4000; C501=10)

b) Absolute standardisation in physical units

5, 00(bar) =

50

200

200

10

(e. g. C500=200; C501=10)