3 setting of the current limit (imax), Commissioning, 3 setting of the current limit (i – Lenze 8240 HVAC Series User Manual

Page 45

Advertising
background image

Commissioning

5-5

UOOuhäáã~_^NMMO

5.3.3

Setting of the current limit (I

max

)

Code

Name

Possible settings

IMPORTANT

Lenze

Selection

Info

C022 I

max

limit

motor mode

150

30

{1 %}

150

C023 I

max

limit

generator mode

80

30

{1 %}

150

Function

The controllers are equipped with a current-limit control which determines the dynamic response

under load. The measured load is compared with the limit values set under C022 for motor load and

under C023 for generator load. If the current-limit values are exceeded, the controller will change

its dynamic response.

Adjustment

The acceleration and decleration time should be set short enough so that the drive can follow the

speed profile without reaching I

max

of the controller.

Drive characteristic when

reaching the limit value

D

During acceleration:
- Expansion of the acceleration ramp.

D

During deceleration:
- Expansion of the deceleration ramp.

D

When the load increases at constant speed:
- When the motor-current limit value is reached:

Reduction of the field frequency to 0.

- When the generator-current limit value is reached:

Increase the field frequency to the maximum frequency (C011).

- Stop the field-frequency change if the load falls below the limit value.

Important

D

In the generator mode the current can only be controlled correctly when you connect a brake unit

or in group drive with energy exchange.

D

For operation with chopper frequencies > 8 kHz, the current limit values should be set to the

currents ”I

max

for 60 s” indicated in the rated data (see chapter 3.3

. (Derating with higher chopper frequencies)