Remove unused fb call parameters, View as function block diagram, L-force | plc designer – Lenze PLC Designer PLC Designer (R3-1) User Manual

Page 310

Advertising
background image

L-force | PLC Designer

Menu Commands sorted by Categories

308

DMS 4.1 EN 03/2011 TD29

12.13.34 Remove Unused FB Call Parameters

Symbol:
This command (category 'FBD / LD / IL') is available only for implementation in FBD. Its
execution will remove all unassigned entries or exits of the FB box focused, that is, all
entries or exits whose assignments are empty or marked by '???'. However, the
minimum number of necessary in- or outputs of the box will be maintained.

12.13.35 View as function block diagram

Shortcut: <Ctrl> + <1>
This command (category 'FBD / LD / IL') is available if you currently are working in the
Ladder Diagram (LD) or Instruction List (IL) view of the POU. It can be used in offline
and online (online not available with the current version) mode.
The LD networks respectively the instruction list will be converted appropriately to FBD
networks. Notice anyway, that there are some special elements, which cannot get
converted
and thus will only be available in the appropriate editor view. Further on
some constructs might not be converted un-ambiguously.
To switch back to the LD view use command View as ladder logic .
To switch back to the IL view use command View as instruction list .

Attention: A proper conversion presumes syntactically correct code. Otherwise parts
of the implementation can get lost.
Note: Concerning the view options for the components of a LD / FBD network notice
the settings in the 'FBD/LD and IL editor Options'.

Advertising