CO Transmitter • 6

Pioneer Operator’s Manual

6.

Connect the two wires to the interconnect terminal strip as follows (see Figure 3.)

Connect the positive wire to the terminal labeled

24V +

.

Connect the feedback wire to the terminal labeled

4/20 FB

.

CAUTION:

Leave the ground wire insulated and disconnected at the transmitter. You will

connect the opposite end of the cable’s ground wire at the Pioneer.

7.

Secure the junction box cover to the junction box.

8.

Route the cable or wires leading from the CO transmitter through one of the conduit
hubs on the bottom of the Pioneer housing.

CAUTION:

Do not route power and transmitter wiring through the same conduit hub. The

power cable may disrupt the transmission of the transmitter signal to the Pioneer.

9.

Connect the wires to the detector terminal strip of the applicable analyzer card as
shown in Figure 3. The detector terminal strip is the 7-point terminal strip (terminals 1
through 7) on the card.

Figure 3: Wiring the CO Transmitter to the Pioneer Gas Monitor

10. At the Pioneer, connect the cable’s ground wire to an available chassis ground. The

grounding screw on each conduit hub is an example of a chassis ground.

CO Detector,
Factory Wired

Jumper Block

Installed To Toxic

Select Header

Individual Amp/Detec tor

Terminals

Not

Used

F actory Set Pot

Red

Not Used

Toxic Amplif ier

Assembly

Black

24V

4/2 0

TOXIC

Z ERO

OXY

B ATT

FB

SPAN

TOXIC

G

GND

FB (4/20)

24V

GRN

BLK

RED

WHT

W

R D

B K

OXY