Alarm 1 setpoint screen

This screen indicates the setpoint and alarm type for Alarm 1. The default setting for the
alarm 1 setpoint for the combustible gas channel is

10

. The default setting for the alarm

type is

RISE

.

To accept the settings and continue the program, press the ENTER button two times.

The program displays the Alarm 2 Setpoint screen.

To update the alarm 1 setpoint:

1.

Use the UP/YES and DOWN/NO buttons to change the setpoint.

2.

Press the ENTER button two times to accept the new setting and continue the
program.

The program displays the Alarm 2 Setpoint screen.

To update the alarm type setting:

1.

Press the ENTER button to select the alarm type setting. (The setting flashes when
it is selected.)

2.

Use the UP/YES or DOWN/NO button to change the setting.

3.

Press the ENTER button to accept the new setting and continue the program.

The program displays the Alarm 2 Setpoint screen.

Alarm 2 setpoint screen

This screen indicates the setpoint and alarm type for Alarm 2. The default setting for the
alarm 2 setpoint for the combustible gas channel is

20

. The default setting for the alarm

type is

RISE

.

To accept the settings and continue the program, press the ENTER button two times.

The program displays the Alarm 3 Setpoint screen.

To update the alarm 2 setpoint:

1.

Use the UP/YES and DOWN/NO buttons to change the setpoint.

2.

Press the ENTER button two times to accept the new setting and continue the
program.

The program displays the Alarm 3 Setpoint screen.

To update the alarm type setting:

1.

Press the ENTER button to select the alarm type setting. (The setting flashes when
it is selected.)

2.

Use the UP/YES or DOWN/NO button to change the setting.

3.

Press the ENTER button to accept the new setting and continue the program.

The program displays the Alarm 3 Setpoint screen.

C h a n n e l

1

A l a r m

1 0

% L E L

C O M B

1

R I S E

C h a n n e l

1

A l a r m

2 0

% L E L

C O M B

2

R I S E