Pioneer Operator’s Manual (PRELIMINARY)

Combustible Gas Transmitter • 21

Slow or No Response/Difficult or Unable to Calibrate

Symptoms

•

The transmitter responds slowly or does not respond during the monthly response
test.

•

Unable to accurately set the zero or response reading during the calibration
procedure.

•

The transmitter requires frequent calibration.

NOTE:

Under “normal” circumstances, the transmitter requires calibration once every
three months. Some applications may require a more frequent calibration
schedule.

Probable causes

•

The calibration cylinder is low, out-dated, or defective.

•

The transmitter is malfunctioning.

Recommended action

1.

Verify that the calibration cylinder contains an adequate supply of a fresh test sample.

2.

If the calibration/response difficulties continue, replace the detector as described later
in this section.

3.

If the calibration/response difficulties continue, contact RKI Instruments, Inc., for
further instruction.

No Display Reading

Symptoms

•

The transmitter is installed, but the display screen is blank for that channel.

NOTE:

If the display screen is blank for all channels, see the troubleshooting guide in
Chapter 5, Maintenance.

Probable causes

•

The channel status setting is set at NO SENSOR/AMP.

Recommended action

1.

Enter the Channel Setup program, and change the channel status setting to ACTIVE/
ONLINE

or SILENCED/OFFLINE.

2.

If the display reading difficulties continue, contact RKI Instruments, Inc., for further
instruction.