CO Transmitter • 16

Pioneer Operator’s Manual

10. Press the ENTER button.

The Span screen appears.

Performing the response test

1.

Screw the regulator into the calibration cylinder.

NOTE:

Once you introduce the test sample to the transmitter, the Span screen “freezes”
and displays each “selected” channel’s highest reading. This feature enables you
to verify the readings at the Pioneer in addition to the “local” test at the

transmitter.

2.

When the reading on the voltmeter stabilizes, verify that the reading is within ± 10%
of the response reading you determined earlier.

NOTE:

If the readings are not within ± 10% of the correct response reading, calibrate the

affected transmitters as described in the Calibration section of this insert.

3.

Unscrew the regulator from the calibration cylinder, then disassemble the calibration
kit as described in the Calibration section of this insert.

NOTE:

If the Pioneer’s display reading(s) is above the alarm 1 setpoint when you return
to the normal screen, the Pioneer will initiate the appropriate alarm condition.
You can view the reading(s) of the “selected” channels on the Fresh Air screen in
the Calibrate program.

To display the Fresh Air screen, press the ESCAPE button, next press the UP/YES

button, then press the ENTER button.

4.

Press the ESCAPE button until the Save screen appears.