Oxygen transmitter, Overview, Specifications – RKI Instruments Pioneer 4W User Manual

Page 77

Advertising
background image

Pioneer Operator’s Manual (PRELIMINARY)

Oxygen Transmitter • 1

Oxygen Transmitter

Overview

This detection insert describes the oxygen transmitter. This insert also describes how to
install, start up, maintain, and calibrate the transmitter and run the Channel Setup
program. A parts list at the end of this insert lists replacement parts and accessories for the
oxygen transmitter.

Specifications

Table 1 lists specifications for the oxygen transmitter. See the specifications in Chapter 1,
Introduction, for specifications that apply to the Pioneer Gas Monitor.

Table 1: Specifications

Target Gas

Oxygen (O

2

)

Sampling Method

Diffusion

Signal Output

4 to 20 mA

Detection Range

0 to 25.0% VOL (by volume)*

Alarm 1 Setpoint

19.5% VOL (decreasing)*

Alarm 2 Setpoint

17.0% VOL (decreasing)*

Alarm 3 Setpoint

23.5% VOL (increasing)*

Response Time

90% in 30 seconds

*

These specifications represent RKI standard settings; however, you can adjust them in the Channel Setup program.