Fail condition, Fail condition indications, Mounting the combustible gas transmitter – RKI Instruments Pioneer 4W User Manual

Page 26: Description, Mounting the oxygen transmitter, Mounting the co transmitter

Advertising
background image

22 • Operation

Pioneer Gas Monitor Operator’s Manual

NOTE:

The alarm 3 relay does not energize if you elect to use it as the channel’s fail relay
in the Channel Setup program (see the “Channel Setup Program” section of the

applicable detection insert in Appendix B, Gas Detectors.)

Responding to an alarm 3 condition

This section suggests response to an alarm 3 condition.

1.

Follow your established procedure for a high level combustible or toxic gas condition
or an increasing oxygen content condition.

2.

After the gas reading falls below the alarm 3 setpoint, press the reset switch to reset
the alarm 3 circuit. Resetting the alarm 3 circuit turns off the ALARM 3 light, and
de-energizes the common and analyzer card alarm 3 relays.

NOTE:

To silence the buzzer while in an alarm 3 condition, press the reset switch.
You cannot de-energize the alarm 3 relays until the gas reading falls below the

alarm 3 setpoint.

Fail Condition

This section describes the audible and visual indications for a fail condition and suggests
response to a fail condition.

Fail condition indications

The Pioneer senses a fail condition for any of the following:

the detector wiring is disconnected or incorrectly connected

the analyzer card is disconnected or incorrectly connected

the display reading is below the fail setpoint

the monitor or detector is malfunctioning

When the Pioneer senses a fail condition, it alerts you as follows:

the FAIL light turns on

the gas reading in fail condition flashes

the buzzer sounds a steady tone

the common fail relay de-energizes

NOTE:

If you elected to use the analyzer card’s alarm 3 relay as an individual fail relay
in the Channel Setup program, the relay de-energizes in a fail condition.
(See the “Channel Setup Program” section of the applicable detection insert in

Appendix B, Gas Detectors.)

Responding to a fail condition

This section suggests response to a fail condition.

1.

Verify that the detector wiring is correctly and securely connected.

2.

Verify that the analyzer card is securely and correctly installed. (The components of
the analyzer card face left when the analyzer card is correctly installed.)

3.

See the troubleshooting guide in the applicable detection insert (Appendix B,
Gas Detectors).