Combustible Gas Transmitter • 1

Combustible Gas Transmitter

Overview

This detection insert describes the combustible gas transmitter. This insert also describes
how to install, start up, maintain, and calibrate the transmitter and run the Channel Setup
program. A parts list at the end of this insert lists replacement parts and accessories for the
combustible gas transmitter.

Specifications

Table 1 lists specifications for the combustible gas transmitter. See the specifications in
Chapter 1, Introduction, for specifications that apply to the Pioneer Gas Monitor.

Table 1: Specifications

Target Gas

Combustible gas

Area Classification

Explosionproof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Signal Output

4 to 20 mA

Detection Range

0 to 100% LEL*

Alarm 1 Setpoint

10% LEL*

Alarm 2 Setpoint

20% LEL*

Alarm 3 Setpoint

50% LEL*

Response Time

90% in 45 seconds

*

These specifications represent RKI standard settings; however, you can adjust them in the Channel Setup program.