Verify the following, Alarm 3, Starting up the pioneer gas monitor – RKI Instruments Pioneer 4W User Manual

Page 22

Advertising
background image

18 • Installation and Start Up

Pioneer Gas Monitor Operator’s Manual

Starting Up the Pioneer Gas Monitor

Perform the following procedure to place the Pioneer into normal operation.

1.

Complete the mounting and wiring procedures described earlier in this chapter.

2.

Complete all installation procedures described in Appendix B, Gas Detectors.

3.

Verify that all wiring connections are correct and secure and the Pioneer’s power
switch is in the OFF position.

4.

Plug in or turn on the incoming power source (AC or DC) at the power source end.

5.

Place the Pioneer’s power switch in the ON position.

NOTE:

To prevent unwanted alarms during warm up, the alarm circuits are not active
for 20 seconds to 2 minutes (depending on warm up) from the time you turn the

power switch on.

6.

Verify the following:

The PILOT light above the display screen is on.

The POWER light on the main circuit board is on.

The pilot light on each analyzer card is flashing.

If the pilot lights are not on or flashing, see the troubleshooting guides in Chapter 5,
Maintenance, and Appendix B, Gas Detectors.

7.

Perform the start-up procedure for each detector as described in Appendix B,
Gas Detectors.