Oxygen Transmitter • 22

Pioneer Operator’s Manual (PRELIMINARY)

10. Reconnect the wiring from the Pioneer to the interconnect terminal strip as shown in

Table 3 and Figure 3, Wiring the Oxygen Transmitter to the Pioneer Gas Monitor.

11. Reconnect the wiring from the (2-point) sensor terminal block in the detector junction

box to the amplifier’s detector terminal strip as shown in Table 4 and Figure 3, Wiring
the Oxygen Transmitter to the Pioneer Gas Monitor.

12. Place the Pioneer’s power switch in the ON position.

13. Calibrate the oxygen transmitter as described in the Calibration section of this insert.

Table 3: Reconnecting the Oxygen Amplifier to the Pioneer Gas Monitor

Amplifier

Interconnect Terminal Strip

Pioneer Analyzer Card

4/20 FB

4-20 (Terminal 5)

24V +

24 V (Terminal 6)

Table 4: Reconnecting the Oxygen Detector to the Amplifier

Sensor

Terminal Block

Amplifier

Interconnect Terminal Strip

+ (white)

OXY W

— (green)

OXY G