Pioneer Operator’s Manual (PRELIMINARY)

Combustible Gas Transmitter • 7

8.

Connect the wires to the detector terminal strip of the applicable analyzer card as
shown in Figure 3. The detector terminal strip is the 7-point terminal strip (terminals 1
through 7) on the card.

Figure 3: Wiring the Combustible Gas Transmitter to the Pioneer Gas Monitor

9.

At the Pioneer, connect the cable’s ground wire to an available chassis ground. The
grounding screw on each conduit hub is an example of a chassis ground.

10. At the Pioneer, insert 3/4 in. NPT conduit plugs in any unused conduit hubs. See

“Parts List” on page 28 for ordering information.

GND

24V

4-20

RED

WHT

GRN

BLK

SENSOR

POWER/SIG

TP+

TP-

1 BLK

2 GRN

3 WHT

4 RED

5 4-20

6 24 V

7 Gnd

Detector Terminal Strip

(on Pioneer Analyzer Card)

Black

Green

White

Red

NOT USED