Pioneer Operator’s Manual (PRELIMINARY)

Combustible Gas Transmitter • 13

Fail setpoint screen

This screen indicates the setpoint and alarm type for the fail alarm. The setpoint is the
display reading at which the alarm is activated. The alarm type controls how the alarm is
activated (rising or falling readings).

The default setting for the fail setpoint for the combustible gas channel is

-10

. The default

setting for the alarm type is

FALL

.

NOTE:

If you selected a measuring options setting of

PPM/LEL

, you can select PPM or

LEL fail and alarm setpoint settings.

To accept the settings and continue the program, press the ENTER button two times.

The program displays the Alarm 1 Setpoint screen.

To update the fail setpoint setting:

1.

Use the UP/YES and DOWN/NO buttons to change the fail setpoint setting.

2.

Press the ENTER button two times to accept the new setting and continue the
program.

The program displays the Alarm 1 Setpoint screen.

To update the alarm type setting:

1.

Press the ENTER button to select the alarm type setting. (The setting flashes when
it is selected.)

2.

Use the UP/YES or DOWN/NO button to change the setting.

3.

Press the ENTER button to accept the new setting and continue the program.

The program displays the Alarm 1 Setpoint screen.

C h a n n e l

1

F a i l

A l a r m

- 1 0

% L E L

C O M B

F A L L