Pioneer Operator’s Manual (PRELIMINARY)

Oxygen Transmitter • 5

Installation

This section describes procedures to mount the oxygen transmitter in the monitoring
environment and wire the transmitter to the Pioneer Gas Monitor.

Mounting the Oxygen Transmitter

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site that is at normal breathing level.

CAUTION:

Mount the oxygen transmitter with the amplifier junction box above the detector

junction box (see Figure 2.)

2.

At the monitoring site, use

1/4 in. screws through the two mounting holes on the left

side of the

amplifier

junction box to secure the e junction box to the vertical mounting

surface (see Figure 2.)

Figure 2: Mounting the Oxygen Transmitter

5.25

in.

5.9

in.

10.5

in.

5.0 in.

Note:

The junction box is 4.63 in. deep.