3. how to wire, Recommended cable, Figure of terminal plate – RKI Instruments GD-70D Series User Manual

Page 23: Specifications of terminal plate, Caution

Advertising
background image

2 Installation

2-3. How to wire

- 23 -

GD-70D

2-3. How to wire


NOTE

To use the pyrolyzer unit (PLU-70), also refer to the individual operating manual.












<Recommended Cable>

For 3-wire type 4 - 20 mA
(common power supply)

Shielded cable of CVVS, etc. (1.25sq) - 3-core

For 4-wire type 4 - 20 mA

Power: Cable of CVV, etc. (1.25sq) - 2-core
Signal: Shielded cable of CVVS, etc. (1.25sq) - 2-core

For 2-wire type DC power-line
communication system (NT)

Shielded twisted-pair cable of KPEV-S, etc. (1.25sq) - 1P

For contact

Cable of CVV, etc. (1.25sq) - max. 6-core

<Figure of Terminal Plate>

1 2 3 4 5 6 7 8 9 10

+ - + -

24VDC

4-20mA

ALM1 contact

ALM2 contact

FAULT contact

NOTE

For the 3-wire type (4 - 20 mA), the terminal 2 is used for common, and the terminals 2(-) and 3(+) are used
to output 4 - 20 mA.
For the NT specification, the terminals 3 and 4 are not used.

<Specifications of Terminal Plate>

Specifications of terminal plate

• Rated voltage: 250 VDC

• Rated current: 16 A











CAUTION

• Be careful not to damage the internal electronic circuit when wiring. In addition, be careful not to apply

stresses on the detector when (overweight) cables are installed.

• The power cables and signal cables must not be installed together with the motor power cables, etc.

When these cables must be installed together for unavoidable reasons, put the power cables and
signal cables in a metal conduit. The conduit must be connected to a grounding circuit.

• When stranded wires are used, prevent wires from contacting each other.

• Use the dedicated handling lever to wire.

Wiring hole

Driver slot

Conductive
part

Cage
clamp/spring

Top handling slot