3. external output operation – RKI Instruments GD-70D Series User Manual

Page 38

Advertising
background image

4 Detection Mode

4-3. External output operation

GD-70D

- 38 -

4-3. External output operation

Specifications

4 - 20 mA

Power-line communication system (NT)

Signal Transmission System

Electric current transmission (non-isolated)

2-wire type DC power-line communication
system

Transmission Path

CVVS

KPEV-S

Transmission Distance

Below 1 km

Below 300 m (depending on the system
designing conditions)

Connection Load Resistance

Below 300 Ω -

c

Detection Mode (No Alarm)

4 - 20 mA (concentration output)

Concentration data

d

Detection Mode (Gas Alarm)

4 - 20 mA (concentration output)

Concentration data, Alarm bits

e

Initial Clear

Depending on the setting of

f

2.5 mA setting: 2.5 mA
4 mA, HOLD, 4-20 mA setting: 4 mA*

Initial bit

f

Maintenance Mode

2.5 mA setting: 2.5 mA
4 mA setting: 4mA*
HOLD Setting: the previous value retained
4-20 mA setting: 4 - 20 mA (concentration output)

Concentration data, Adjustment bit

g

Alarm Test

Output ON setting: 4 - 20 mA (concentration output)
Output OFF setting: In accordance with setting of

f

Concentration data, Adjustment bit, Test bit

h

Fault Alarm

0.5 mA (Fixed)

Fault bits

i

Inhibit

Depending on the setting of

f

2.5 mA setting: 2.5 mA
4 mA, HOLD, 4 - 20 mA setting: 4 mA*

Concentration data, Adjustment bit, Inhibit bit

j

Power Off

0 mA

Signal OFF

* OSU - 0 - 25 vol% is equivalent of AIR (20.9 vol% = 17.4 mA)