4 Detection Mode

4-1. Gas alarm activation

- 35 -

GD-70





4

Detection Mode




4-1. Gas alarm activation



Gas alarm: Activated when the concentration of detected gas reaches or exceeds the alarm setpoint.
<<Auto-Reset Operation>>

NOTE

The alarm setpoint (first alarm and second alarm) is entered before it is delivered from the factory. Although
the alarm delay time (standard: 2 seconds) is enabled in the detector to prevent a false activation, you can
disable it if not needed.

<Display Operation>

Gas Concentration Display

In case of over the detection range (Over Scale), "∩∩∩∩" is displayed on the LCD.

Power Indicator Lamp (POWER: Green)

This lights up continuously.

Alarm Indicator Lamp (ALM1: Red), (ALM2: Red)

The alarm consists of two steps. Each of them lights up when respective alarm setpoint is reached or
exceeded.