1 Overview

1-3. Product specifications

- 7 -

GD-70D

1-3. Product specifications

<Common Specifications>

Concentration
Display

Character LCD (Digital and Bar Meter Display)

Suction Flow Rate

0.5L/min

±10%

Power Display

POWER lamp on (green)

Displays

Gas name display/Flow rate indicator/Mode display/Communication status
display/Pyrolyzer connection display

Gas Alarm Display

First: ALM1 lamp on (Red)/Second: ALM2 lamp on (Red)

Gas Alarm
Activation

Auto-reset

Gas Alarm Contact

No-voltage contact 1a or 1b (2 step independent)
de-energized (energized at a time of alarm) or energized (de-energized at a
time of alarm)

Fault Alarm/Self
Diagnosis

System abnormalities/Sensor abnormalities/Flow Rate
abnormalities/Communication abnormalities/Pyrolyzer abnormalities

Fault Alarm
Display

FAULT lamp on (Yellow)/Detail display

Fault Alarm
Activation

Auto-reset

Fault Alarm
Contact

No-voltage contact 1a or 1b
de-energized (energized at a time of alarm) or energized (de-energized at a
time of alarm)

Contact Capacity

125 VAC - 0.25A/24 VDC - 0.5A (Resistant load)

Recommended
Contact Cable

Cable of CVV, etc. (1.25sq) - max. 6-core

Functions

White backlight/Alarm delay/Suppression/Zero follower/Sensitivity correction/
Flow control/Calibration history/Alarm trend history/Event history

Tube Connecting
Hole

Rc1/4 (O.D Φ6-1t half-union for Teflon tube<PP>supplied)

Initial Clear

Approx. 25 seconds

Structure

Box type/Wall mounted type

External
Dimensions

Approx. 70(W)x120(H)x145(D) mm (projection potions excluded)

Weight

Approx. 0.9 kg

Outer Color

Gas detector: grey
Front door: white

<Specifications for Each Model>

Model

GD-70D

GD-70D-NT

Transmission
System

3-wire type analog transmission
(Common Power Supply <Power,
Signal, Common>)
or 2-wire type analog transmission

2-wire type DC power-line
communication

Transmission
Specification

4 - 20 mA DC (no-insulation/load
resistance under 300Ω)

DC power-line communication
system

Recommended
Transmission
Cable

Shielded cable of CVVS, etc. (1.25sq)
3-core or 2-core

Shielded twisted-pair cable
(1.25sq) of KPEV-S, etc. - 1P

Recommended
Power Cable

Cable of CVV, etc.(1.25sq) - 2-core
(Those for 3-wire type are common with
the transmission cable.)

(Common with the transmission
cable)

Power Supply

24VDC

±10%

24VDC

±10%

(Dedicated line by blocking filter)

Advertising