Detection principle

GD-70D

- 78 -

Safety of the radioisotope 241Am (37 KBq) used in the pyrolysis-particle type
sensor


The pyrolysis-particle type sensor installed in the gas detector uses the radioisotope 241Am radiation
source (18.5 KBq x 2 = 37 KBq).

A specified designing certification device must satisfy the specified threshold for "1 cm dose equivalent
rate at a point 10 cm away from the surface of the device" as a certificate condition, which is the following
value (tolerable amount).

Tolerable

amount

1 cm dose equivalent rate at a
point 10 cm away from the
surface of the device

1µSv•h

-1



This detector which uses radioisotope

241

Am radiation source (18.5 KBq x 2 = 37 KBq) has the following 1

cm dose equivalent rate at a point 10 cm away from its surface, meaning that it completely satisfies the
certification condition.

1 cm dose equivalent rate at a point 10 cm away from the surface
of the sensor (calculated value)

cm

r

Q

D

1

2

Γ

=

( )

019

.

0

00524

.

0

1

.

0

10

5

.

18

2

2

3

=

Ч

Ч

=

[µSv•h

-1

]

Q

: Amount of radioisotope 2 x 18.5 x 10

-3

[MBq] =(37KBq)

cm

1

Γ

: 1 cm dose equivalent rate constant of

241

Am 0.00524 [µSv•m

2

•MBq

-1

•h

-1

]

r

: Distance from radiation source 0.1[m]





It is certified as a safety device, provided that it is used in accordance with the certification conditions
specified in the "Safety Manual".