8 Maintenance

8-1. Maintenance intervals and items

GD-70

- 62 -





8

Maintenance





This is a critical instrument for disaster-proof and safety.
To maintain the performance of the detector and improve the reliability of disaster-proof and safety, perform
a regular maintenance.

NOTE

To use the pyrolyzer unit (PLU-70), also refer to the individual operating manual.


8-1. Maintenance intervals and items

• Daily maintenance: perform a maintenance before beginning to work.

• Monthly maintenance: perform a maintenance on the alarm circuit (alarm test) once a month.

• Regular maintenance: perform a maintenance once or more for every six months to maintain the

performance as a safety device.

Maintenance
item

Maintenance content

Daily

maintenance

Monthly

maintenance

Regular

maintenance

Power supply
check

Verify that the power lamp lights up.

Concentration
display check

Verify that the concentration display
value is zero (or 20.9 vol% on the oxygen
deficiency meter). When the reading is
incorrect, perform the zero adjustment
after ensuring that no other gases exist
around it.

Flow rate
check

See the flow rate indicator to check for
abnormalities.

Filter check

Check the dust filter for dust or clogging.

Alarm test

Inspect the alarm circuit by using the
alarm test function.

Span
adjustment

Perform the sensitivity calibration by
using the calibration gas.

Gas alarm
check

Check the gas alarm by using the
calibration gas.