7 Regular Maintenance Mode

- 61 -

GD-70D

<Energized/De-Energized Contact Setting "2-10" - "SET 6">

Energized/De-Energized Contact Setting

PW A1 A2

F

LCD

SET 6. RLY PTRN

Press the SET key.

● ○ ○ ○

SET 6

RLY PTRN

MAINTENANCE

● ○ ○ ○

nd

AL1 RLY

MAINTENANCE

▲/▼

nE

AL1 RLY

MAINTENANCE

First Alarm Contact
Setting

Select either
nd(De-Energized)/nE(Energi
zed), and then press the
SET key to confirm the
selection. (Press the MODE
key to skip this menu.)

● ○ ○ ○

nd

AL2 RLY

MAINTENANCE

▲/▼

nE

AL2 RLY

MAINTENANCE

Second Alarm Contact
Setting

Select either nd
(De-Energized)/nE
(Energized), and then press
the SET key to confirm the
selection. (Press the MODE
key to skip this menu.)

● ○ ○ ○

nd

FLT RLY

MAINTENANCE

▲/▼

nE

FLT RLY

MAINTENANCE

Fault Alarm Contact
Setting

Select either nd
(De-Energized)/nE
(Energized), and then press
the SET key to confirm the
selection. (Press the MODE
key to skip this menu.)

Return

to

SET 6. RLY PTRN

NOTE

When De-energized is selected, the relay is energized and activated in response to an alarm (de-energized
at a normal environment).
• When the contact "a" is used, it is open at a normal environment while closed in response to an alarm.
• When the contact "b" is used, it is activated conversely.

When Energized is selected, the relay is energized at a normal environment (de-energized in response to
an alarm).
• When the contact "a" is used, it is closed at a normal environment while open in response to an alarm.

In addition, it is closed when the power is OFF.

• When the contact "b" is used, it is activated conversely.