Rockwell Automation 20-COMM-I Interbus Adapter User Manual

Page 26

Advertising
background image

3-4

Configuring the Adapter

4. Interbus requires the network I/O mapping to be configured first in

the adapter. CMD software will read this configuration online when
it is configuring the scanner.

Process Input Data Description (PIDD) words map input data on the
network (data seen as inputs to the scanner and controller program).
Example input data includes Logic Status, Feedback and Datalinks
(Datalink x1 Out). Up to 9 words of input data can be mapped.

Process Output Data Description (PODD) words map output data on
the network (data sent as outputs from the scanner and controller
program). Example output data includes Logic Command, Reference
and Datalinks (Datalink x1 In). Up to 9 words of output data can be
mapped.

The following indexes are used to select the I/O data:

Table 3.1 PIDD/PODD Indexes

Value
(Hex)

Value
(Dec)

Selects

2F9A

12186

Logic Status

2F9B

12187

Feedback

2FA4

12196

Datalink A1 Out

2FA5

12197

Datalink A2 Out

2FA6

12198

Datalink B1 Out

2FA7

12199

Datalink B2 Out

2FA8

12200

Datalink C1 Out

2FA9

12201

Datalink C2 Out

2FAA

12202

Datalink D1 Out

2FAB

12203

Datalink D2 Out

Value
(Hex)

Value
(Dec)

Selects

2F98

12184

Logic Command

2F99

12185

Reference

2F9C

12188

Datalink A1 In

2F9D

12189

Datalink A2 In

2F9E

12190

Datalink B1 In

2F9F

12191

Datalink B2 In

2FA0

12192

Datalink C1 In

2FA1

12193

Datalink C2 In

2FA2

12194

Datalink D1 In

2FA3

12195

Datalink D2 In

Input

Output