Configuring the Interbus Scanner

The scanner mapping correlates to SLC addressing as follows:

The mapping in the scanner is set up in bytes. Inputs to the scanner start
at byte #512 and outputs start at byte #0.

PIDD/PODD parameter settings in the adapter determine the length of
I/O data mapped. In the example, each device is configured for 9 words
(144 bits) of inputs and 9 words (144 bits) of outputs, the maximum
allowed for each device.

(USC/4) Output SLC (USC/4) Input SLC

0
1

63
64
65

511

O:x.0(high)
O:x.0(low)

O:x.31(low)
M0:x.0(high)
M0:x.0(low)

M0:x.223(low)

512
513

575
576

1023

I:x.0(high)
I:x.0(low)

I:x.31(low)
M1:x.0(high)
M1:x.0(low)

M1:x.223(low)

Scanner

Scanner