Powerflex 70 settings to use with ladder examples, Rslogix 500 sst interbus scanner configuration – Rockwell Automation 20-COMM-I Interbus Adapter User Manual

Page 47

Advertising
background image

Configuring the Interbus Scanner

4-15

PowerFlex 70 Settings to use with Ladder Examples

The following parameters should be configured to use the example
ladder logic program.

PowerFlex 70

RSLogix 500 SST Interbus Scanner Configuration

The SST Interbus scanner is configured by clicking on the I/O
Configuration in RSLogix500. The SST-IBS-SLC has an ID Code of
13635. The following settings are used by the example ladder logic
program, as shown in

Figure 4.18

and

Figure 4.19

.

Parameter Name

Value

Description

90

Speed Ref A Sel

22

DPI Port 5 (20-COMM-I) provides the
Reference

300

Data In A1

140

Pr. 140 [Accel Time 1]

301

Data In A2

142

Pr. 142 [Decel Time 1]

302

Data In B1

100

Pr. 100 [Jog Speed]

303

Data In B2

155

Pr. 155 [Stop Mode A]

304

Data In C1

101

Pr. 101 [Preset Speed 1]

305

Data In C2

102

Pr. 102 [Preset Speed 2]

306

Data In D1

103

Pr. 103 [Preset Speed 3]

310

Data Out A1

140

Pr. 140 [Accel Time 1]

311

Data Out A2

142

Pr. 142 [Decel Time]

312

Data Out B1

100

Pr. 100 [Jog Speed]

313

Data Out B2

155

Pr. 155 [Stop Mode A]

314

Data Out C1

101

Pr. 101 [Preset Speed 1]

315

Data Out C2

102

Pr. 102 [Preset Speed 2]

316

Data Out D1

103

Pr. 103 [Preset Speed 3]

20COMM-UM007A-EN-P.book Page 15 Tuesday, January 22, 2002 10:52 AM

Advertising