Pcp communications – Rockwell Automation 20-COMM-I Interbus Adapter User Manual

Page 65

Advertising
background image

Using Explicit Messaging (PCP Communications)

6-3

Peripheral Communications Protocol (PCP) messages are used for
explicit messaging, which is not part of the normal Interbus
I/O data scan. The scanner takes care of all of the details of
establishing a connection for PCP communication services. PCP
communications can be used to:

• Read or write DPI Host (PowerFlex 70, etc.) parameters

• Read or write 20-COMM-I parameters

• Read DPI Host (PowerFlex 70, etc.) faults

• Read 20-COMM-I events

The Command Interface for the SST SLC Interbus scanner must be
enabled for PCP Communications to take place:

• Bit 12 of word 1 in the G File must be set

• Word 5 in the G File must be set to the length of process data

required in the M Files. This value can range from 0 to 224

• Word 6 in the G File must be set to the maximum length of the

command buffer. This value can range from 0 to 128 and must be
non-zero to enable the buffer.

PCP Communications

Name

PCP - Index Value Range Access Rights Description

Hex

Decimal

Host
Parameters

3001 to
(3001 +n)

12289 to
(12289 + n)

Host Parameter
Dependent

3001 (12289 Dec) =
Parameter 1 - etc.

Host Fault
Queue

2FF9 to 3000 12281 to

12288

Read Only

Host fault queue
containing up to 8 faults

20-COMM-I
Parameters

2FB6 to 2FEE 12214 to

12270

Parameter
Dependent

2FB6 (12214 Dec) =
Parameter 1 - etc.

20-COMM-I
Event Queue

2FAE to 2FB5 12206 to

12213

Read Only

Adapter event queue (8
events)

20COMM-UM007A-EN-P.book Page 3 Tuesday, January 22, 2002 10:52 AM