Word
Value
(Decimal)
Value
(Hexadecimal)
Description
0
8224
2020
Fixed to 2020h by the SLC
1
4096
1000
Enables the command interface between the SLC
and the USC/4
2
0
0
Use the CMD specified Bus Update Time
3
0
0
Use the CMD specified Bus Warning Time
4
0
0
Use the CMD specified Bus Timeout
5
0
0
The number of words used at the beginning of the
M files for Inputs and Outputs
6
128
80
Maximum data size for commands and replies sent
between the SLC and the scanner
20COMM-UM007A-EN-P.book Page 16 Tuesday, January 22, 2002 10:52 AM