Rockwell Automation 20-COMM-I Interbus Adapter User Manual

Page 48

Advertising
background image

4-16

Configuring the Interbus Scanner

Figure 4.18 Scanner I/O Configuration

Figure 4.19 Scanner_G_ files

G File Data Information:

Refer to the SST-IBS-SLC User’s Guide for more information.

Word

Value

(Decimal)

Value

(Hexadecimal)

Description

0

8224

2020

Fixed to 2020h by the SLC

1

4096

1000

Enables the command interface between the SLC
and the USC/4

2

0

0

Use the CMD specified Bus Update Time

3

0

0

Use the CMD specified Bus Warning Time

4

0

0

Use the CMD specified Bus Timeout

5

0

0

The number of words used at the beginning of the
M files for Inputs and Outputs

6

128

80

Maximum data size for commands and replies sent
between the SLC and the scanner

20COMM-UM007A-EN-P.book Page 16 Tuesday, January 22, 2002 10:52 AM