7-6

Troubleshooting

Events

Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:

Code

Event

Description

1

No Event

Empty event queue entry.

2

DPI Bus Off
Flt

A bus-off condition was detected on DPI. This event may be
caused by loose or broken cables or by noise.

3

Ping Time Flt A ping message was not received on DPI within the specified

time.

4

Port ID Flt

The adapter is not connected to a correct port on a DPI product.

5

Port Change
Flt

The DPI port changed.

6

Host Sent
Reset

The DPI product issued this because it was reset.

7

EEPROM
Sum Flt

The EEPROM in the adapter is corrupt.

8

Online @
125kbps

The adapter and DPI product are communicating at 125kbps.

9

Online @
500kbps

The adapter and DPI product are communicating at 500kbps.

10

Bad Host Flt

The adapter was connected to an incompatible product.

11

Dup. Port Flt

Another peripheral with the same port number is already in use.

12

Type 0 Login

The adapter has logged in for type 0 control.

13

Type 0 Time
Flt

The adapter has not received a type 0 status message within
the specified time.

14

DL Login

The adapter has logged into a Datalink.

15

DL Reject Flt The host rejected an attempt to log in to a Datalink because the

Datalink is not supported or is used by another peripheral.

16

DL Time Flt

The adapter has not received a Datalink message within the
specified time.

17

Control
Disabled

The adapter has sent a “Soft Control Disable” command to the
DPI product.

18

Control
Enabled

The adapter has sent a “Soft Control Enable” command to the
DPI product.

19

Message
Timeout

A Client-Server message sent by the peripheral was not
completed.

20

DPI Fault Msg The DPI Host has faulted.

21

DPI Fault
Clear

The user cleared a fault in the adapter.

22

Normal
Startup

Peripheral completes a normal startup.

23

Net Comm Flt The adapter detected a fault condition on the Interbus network.

24

Fault Cfg
Error

The peripheral detected a 32-bit fault configuration Reference
when the Host supports only a 16-bit Reference, or vice-versa.