Page 53

Using I/O Messaging
5-3
An image that uses 32-bit words for Reference and Datalinks would
change the I/O image as follows:
illustrates an example of an I/O image that does not use all of
the I/O data. Only the Logic Command/Reference and Datalink B are
enabled. In this example, the Reference is a 32-bit word, and Datalinks
are 16-bit words.
Figure 5.2 Example I/O Image with Only Logic/Reference and Datalink B Enabled
LSW = Least Significant Word (Bits 15 - 0)
MSW = Most Significant Word (Bits 31 - 16)
Word
I/O
0
Logic Command/Status
1 - 2
Reference/Feedback
3 - 6
Datalink A1/A2
7 - 10
Datalink B1/B2
Controller
Scanner
Adapter
PowerFlex Drive
Interbus
DPI
Output
Image
(Write)
Input
Image
(Read)
0 Logic Status
1 Feedback (LSW)
2 Feedback (MSW)
3 Datalink Out B1
4 Datalink Out B2
0 Logic Command
1 Reference (LSW)
2 Reference (MSW)
3 Datalink In B1
4 Datalink In B2
Logic Status
Feedback
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Word and I/O
Logic Command
Reference
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
20COMM-UM007A-EN-P.book Page 3 Tuesday, January 22, 2002 10:52 AM