5-6

Using I/O Messaging

The Interbus example program uses a SLC processor with an SST
Interbus scanner (SST-IBS-SLC) in the first slot of the rack and will
work with PowerFlex 70 or PowerFlex 700 drives.

Function of the Example Program

The program is written for (2) drives on the network and demonstrates
using:

• Logic Command / Reference

• Logic Status / Feedback

• Datalinks

• PCP Read / Write (See

Chapter 6

.)

Adapter Settings

The 20-COMM-I node addresses are set via CMD software to:

• “1.0” (CR=2) for Station 1

• “2.0” (CR=3) for Station 2

See

Chapter 4

,

Adapter Configuration Settings to use with Ladder

Examples

.

PowerFlex 70 Settings

See

Chapter 4

,

PowerFlex 70 Settings to use with Ladder Examples

.

SST Scanner Settings

See

Chapter 4

,

RSLogix 500 SST Interbus Scanner Configuration

.

SLC Example Ladder Logic Program