Install Your FLEX I/O Input Module 9

Methods of wiring the terminal base units are shown in the illustration below.

ATTENTION

Do not daisychain power or ground from the terminal base unit to any
AC or DC digital module terminal base unit.

Digital Input

Module

Analog

Module

Analog

Module

Analog

Module

Digital Output

Module

Digital Input

Module

TC/RTD/mV

Module

Analog

Module

TC/RTD/mV

Module

TC/RTD/mV

Module

TC/RTD/mV

Module

TC/RTD/mV

Module

Daisychain

Individual

Combination

24V DC

24V DC

24V DC

24V DC

24V DC

24V DC

45318

Wiring when total current draw is less than 10 A

Wiring when total current draw is less than 10 A

Thermocouple, RTD, Millivolt wiring separate from digital wiring.

Total current draw through any base unit must not be greater than 10 A