Calibrate Your Module

Overview

This chapter provides the tools and equipment, and procedure for calibrating
your FLEX I/OThermocouple, RTD, and mV input module.

When and How to
Calibrate Your FLEX I/O
Module

This module is shipped to you already calibrated. If a calibration check is
required, the module must be in a FLEX system. We recommend recalibrating
your module, if the module is going to be used in an environment with
temperature other than 25 °C (77 °F) and 30% humidity.

Calibration can be accomplished using the manual calibration procedure
described in the following sections.

Topic

Page

When and How to Calibrate Your FLEX I/O Module

39

Tools and Equipment

40

Calibrate Your Input Module

40

Calibration Setup

41

Wiring Connections for Calibrating the Thermocouple and RTD

Input Module

41

Read and Write Words for Calibration

42

EDT Calibration Command and Command Data Summary

44

Offset Calibration

45

Gain Calibration

46

Current Source Calibration

47

Cold Junction Calibration

49

Channel Loop Compensation Calibration

49

Chapter Summary

49

ATTENTION

Perform module calibration periodically, based on your application, or
at least once a year. Module calibration may also be required to
remove module error caused by aging components in your system.
Offset calibration must be done first, followed by gain calibration.

IMPORTANT

You must use a 1794-TB3G or 1794-TB3GS terminal base when
calibrating this module.