Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 45

Advertising
background image

Publication 1794-6.5.12 - September 2011

Read and Write Configuration Maps for the FLEX I/O Module 33

Read Word 3

00…15

(00…17)

Channel 3 Input data

Read Word 4

00…15

(00…17)

Channel 4 Input data

Read Word 5

00…15

(00…17)

Channel 5 Input data

Read Word 6

00…15

(00…17)

Channel 6 Input data

Read Word 7

00…15

(00…17)

Channel 7 Input data

Read Word 8

00…07

Underrange bits

– these bits are set if the input

signal is below the minimum range of the input

channel.

Bit 00 corresponds to channel 0…bit 07 corresponds

to channel 7.

08…15

(10…17)

Overrange bits

– these bits are set if 1), the input

signal is above the maximum range of the input

channel; or 2), an input is disconnected.

Bit 08 (10) corresponds to channel 0, bit 09 (11)

corresponds to channel 1, and so on.

Read Word 9

00…03

Diagnostic bits

– represent module configuration

and/or hardware errors.
Bit 03

02

01

00

0

0

0

0

Reserved for factory use

0

0

1

0

Improper module

configuration

0

1

1

0

RAM

f

ault

0

1

1

1

EEPROM fault

0001, 0100, and 0011…1111 Reserved for

factory use

04

Series of Unit (SAB) – 0 = Series A, 1 = Series B

05…06

Cold junction compensation fault bits

– These

bits are set (1) when the corresponding cold junction

compensator lead is broken, unattached or shorted,

and the thermocouple is set to "external

compensation.” Bit 05 corresponds to CJC1, and bit

06 to CJC2.

07

Not used

08…15

(10…17)

Fault alarm bits

– An alarm bit is set (1) when an

individual input lead opens (broken, disconnected). If

the alarm is enabled, the channel reads maximum

value. Bit 08 (10) corresponds to input channel 0, bit

09 (11) to channel 1, and so on.