Environmental specifications, General specifications – Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 67

Advertising
background image

Publication 1794-6.5.12 - September 2011

Specifications 55

Temperature code, North

American

T4A

Enclosure type rating

None (open-style)

Wire size

Determined by installed terminal base

Signal conductors

Thermocouple

Millivolt

Wire type

Use appropriate shielded thermocouple wire

(2)

Belden 8761

Shielded on signal ports

Wiring category

(1)

2 – on signal ports

3 – on power ports

Terminal screw torque for

cage-clamp terminal base

Determined by installed terminal base

(1)

Refer to the thermocouple manufacturer for proper thermocouple extension.

(2)

Use this category information for planning conductor routing as described in Industrial Automation Wiring and
Grounding Guidelines, Allen-Bradley publication

1770-4.1

.

Environmental Specifications

Attribute

Value

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F) (1794-IRT8, 1794-IRT8K)

-20…70 °C (-4…158 °F) (1794-IRT8XT)

Temperature,

non- operating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating

Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock

operating

nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):

30 g

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

General Specifications

Attribute

Value

Advertising