Troubleshoot the Module

The FLEX I/O Thermocouple, RTD, and mV module returns diagnostics to
the processor in Word 9 of the block transfer read (BTR) file. These
diagnostics give you information on the status or condition of the module.

Chapter Summary

This chapter specified the different status indicators that would help the user
troubleshoot the module.

Blinking

(when faults

are enabled,

and bit set)

Indicates a noncritical fault (such as open sensor). Input data set to

maximum, and indicator flashes at about 1 Hz rate.

Power

Off

Module not powered

Green

On

Module receiving power

Status Indicators

Indicator

Color

State

Description

Diagnostic Bits in Word 9

Word

Dec. Bits
(Octal Bits)

Description

Read Word 9

00…03

Diagnostic bits

– represent module configuration

and/or hardware errors.
Bit 03

02

01

00

0

0

0

0

Reserved for factory use

0

0

1

0

Improper module

configuration

0

1

1

0

RAM

f

ault

0

1

1

1

EEPROM fault

0001, 0100, and 0011…1111 Reserved for

factory use

04

Series of Unit (SAB) – 0 = Series A, 1 = Series B

05…06

Cold junction compensation fault bits

– These

bits are set (1) when the corresponding cold junction

compensator lead is broken, unattached or shorted,

and the thermocouple is set to "external

compensation.” Bit 05 corresponds to CJC1, and bit

06 to CJC2.

07

Not used

08…15

(10…17)

Fault alarm bits

– An alarm bit is set (1) when an

individual input lead opens (broken, disconnected). If

the alarm is enabled, the channel reads maximum

value. Bit 08 (10) corresponds to input channel 0, bit

09 (11) to channel 1, and so on.