18

Install Your FLEX I/O Input Module

Wiring Connections for the FLEX I/O Input Module

Connect the following:

Input types

H

L

+

-

Shield

(1)

(1)

Terminals 37, 38 and 39 and 46, 47 and 48 are for cold junction compensation, with 38 and 47
as chassis GND.

RTD – 2-wire

1

2

RTD – 3-wire

3

1

2

RTD – 4-wire

1a

2a

1

2

Thermocouple

1

2

Millivolt

1

2

CJC Sensor

Input

+

Chassis
Ground

-

CJC Tail

(1)

(1)

Terminals 37, 38, and 39, and 46, 47, and 48 are for cold junction compensation, with 38
and 47 as chassis GND. Connect the tail of CJC1 to terminal 5 and CJC2 to terminal 12
if channels 0…3 or 0…7 are configured for thermocouples. Connect the tail of CJC1 to
terminal 22 and CJC2 to 29 if channels 4…7 are configured for thermocouples.

CJC1

C-37

C-

38

C-

39

A-5 (B-22)

CJC2

C-46

C-

47

C-

48

A-12 (B-29)

Terminal Base Unit Wiring Connections

1794-TB3G, 1794-TB3GK, and 1794-TB3GS Terminal
Base Units

(1)

(1)

Terminals 37, 38, and 39, and 46, 47 and 48 are for cold junction compensation. Terminals 16, 33
and 40…45 are chassis ground. Connect tail of CJC1 to terminal 5 and CJC2 to 12 if channels
0…3 or 0…7 are thermocouples. Connect tail of CJC1 to terminal 22 and CJC2 to 29 only if
channels 4…7 are used.

RTD or TC
Channel

High Signal
Terminal (H)

Low
Signal
Terminal (L)

RTD Source
Current (+)

Signal
Return (-)

0

A-1

A-2

A-0

A-3

1

A-5

A-6

A-4

A-7

2

A-9

A-10

A-8

A-11

3

A-13

A-14

A-12

A-15

4

B-18

B-19

B-17

B-20

5

B-22

B-23

B-21

B-24

6

B-26

B-27

B-25

B-28

7

B-30

B-31

B-29

B-32

+24V DC Power

34 and 50

24V DC Common 35 and 51

1

2

1
3
2

1
1a

2

2a

1

2

1

2

2-wire

3-wire

4-wire

Thermocouple

RTD

Millivolt

+

-

mV

45332

45359