Cold junction calibration, Channel loop compensation calibration, Chapter summary – Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 61

Advertising
background image

Publication 1794-6.5.12 - September 2011

Calibrate Your Module 49

Cold Junction Calibration

Both cold junction compensation inputs must be calibrated at at the same
time. To calibrate both at once, proceed as follows:

1. Connect 10 K

Ω

, 0.5% resistors across terminals 37 and 39 (CJC 1) and

terminals 46 and 48 (CJC 2).

2. Apply power to the module for 20 minutes before calibrating.

3. Initiate a write to the module with 2404 (hex) value in the EDT

command location (word 3, bits 00…15).

4. Monitor the EDT response location (read word 11, bits 00…15) for an

echo of the EDT command.

If the EDT response word reads 80FF (hex), repeat step 3. Make sure that
sufficient time is allowed for the module to respond to your request. If there is
no change, calibration has failed. Check the wiring and try again.

Channel Loop Compensation Calibration

Each 2-wire RTD can be calibrated individually, or at the same time. Proceed
as follows.

1. Short circuit the end of each input cable at the RTD element. Do this

for all the channels to be calibrated.

2. Apply power to the module for 20 minutes before calibrating.

3. Initiate a write to the module with 2403(hex) (calibrate all channels) in

the EDT command location (write word 3, bits 00…15). For individual
channel calibrations, use 04X3 (hex) (0403, 0413, 0423, ...0473).

4. Monitor the EDT response location (read word 1X, bits 00…15) for an

echo of the EDT command.

If the EDT response word reads 80FF (hex), repeat step 3. Make sure that
sufficient time is allowed for the module to respond to your request. If there is
no change, calibration has failed. Check the wiring and try again.

Chapter Summary

This chapter provided the user with instructions on how to calibrate your
FLEX I/O Thermocouple, RTD, and mV input module.