Chapter 6, 6 – troubleshoot the module, Overview – Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 63: Module indicators, Troubleshoot the module, Overview module indicators, Chapter

Advertising
background image

51

Publication 1794-6.5.12 - September 2011

Chapter

6

Troubleshoot the Module

Overview

This chapter provides a description of the different status indicators for the
FLEX I/O Thermocouple, RTD, and mV module to help you troubleshoot.

Module Indicators

The FLEX I/O module has one status indicator (PWR) that is On when
power is applied to the module, and one fault indicator (F) for each input.

IN 0

IN 2

IN 4

IN 6

IN 1

IN 3

IN 5

IN 7

TC RTD INPUT 8 CHANNEL

3

1794-IRT8

PWR

F

F

F

F

F

F

F

F

A

– Insertable label for writing individual input designations

B

– Fault Indicator - indicates noncritical fault

C

– Power Indicator - indicates power applied to module A

A

B

C

Status Indicators

Indicator

Color

State

Description

Fault

Red

On

At power up – Channel 0 indicator lights at power up until all internal

diagnostics are checked. After successful power up, the indicator

goes off if no fault is detected and the module has started

communicating with an adapter.

After successful power up – Indicates a critical fault, such as

diagnostic failure. If channel indicator stays solid red after power up,

there is an internal module error. Try cycling power. If problem

persists, replace module.

If channel indicator continues to blink after power up, communication

between the module and the adapter has not been established.