Program Your Module with PLC Family Processors 61

PLC-5 Family Processor

Block transfer instructions with the PLC-5 processor use a control file and a
data file. The block transfer control file contains the data table section for
module location, the address of the block transfer data file and other related
data. The block transfer data file stores data that you want transferred to the
module (when programming a BTW) or from the module (when programming
a BTR).

The programming terminal prompts you to create a control file when a block
transfer instruction is being programmed. A different block transfer control
file is used for the read and write instructions for your module.

13

U

IRT8 BTR

Error Bit

B17:0

EN

BTR

BLOCK TRANSFER READ
Rack
Group
Slot

Data File

3
2
1

N18:101

Length

Control

0

B17:0

EN

BTW

BLOCK TRANSFER WRITE
Rack
Group
Slot

Data

3
2
1

N18:1

DN

Length

Control

0

B17:0

5

B17:0

B17:0

15

ER

DN

ER

Rung M:0
The IRT8 module is located in rack 3, I/O group 2, slot 1. The control file is a 10 word

file starting at B17:0 that is shared by the BTR/BTW. The data obtained by the PLC3

processor is placed in memory starting at location N18:101, and with the default length

of 0, is 11 words long.

IRT8 BTR

Done Bit

IRT8 BTR/BTW
Control Block

The IRT8 module is located in rack 3, I/O group 2, slot 1. The control file is a 10 word

file starting at B17:0 that is shared by the BTR/BTW. The data sent by the PLC-3

processor to the IRT8 module is from PLC memory starting at N18:1, and with the default

length of 0, is 4 words long.

13

IRT8 BTR

Error Bit

B17:0

IRT8 BTW

Done Bit

IRT8 BTR/BTW
Control Block

3

B17:0

3

B17:0

U

IRT8 BTW

Error Bit

IRT8 BTW

Error Bit

PLC-3 Processor

Program Example