Gain calibration – Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 58

Advertising
background image

Publication 1794-6.5.12 - September 2011

46

Calibrate Your Module

3. Initiate a write to the module with the appropriate value in the EDT

command location (write word 3, bits 00…15), as shown above.

4. Monitor the EDT response location (read word 11 bits 00…15) for an

echo of the EDT command. Depending on which command you sent, it
should show 241X Hex.

If the EDT response word reads 80FF (hex), repeat the step 3. Make
sure that sufficient time is allowed for the module to respond to your
request. If there is no change, calibration has failed. Check the wiring
and try again.

5. Set the precision millivolt source to the value required for a gain of 2.

Repeat steps 3 and 4 for gain 2. Repeat for each gain setting.

6. When all offset calibrations are successful, proceed to the gain

calibration.

Gain Calibration

After completing the offset calibration, proceed with the gain calibration.

1. Connect a precision millivolt source across each input channel. Set the

source to 320.00 mV for a gain of 1. Connect all (L) signal terminals
together and attach to the positive lead from the precision voltage
source. Connect all (-) signal terminals together and attach to the
negative lead.

8

-10.00 + 0.008 mV

2413

9235

05

0

7

3

16

-9.00 + 0.004 mV

2414

9236

05

0

7

4

32

1.000 + 0.002 mV

2415

9237

05

0

7

5

EDT Commands for Offset Calibration

All Channels

Single Channel

EDT Command

EDT
Command
Dec. or Hex
Bits 8

15

EDT Command
Data
Dec. or Hex

Gain
Selected

Input (mV)

Hex

Decimal

Bits
4

7

Bits
0

3