Publication 1794-6.5.12 - September 2011

54

Specifications

Isolation voltage

(continuous voltage

withstand rating)

50V (continuous), Basic Insulation Type

Type tested @ 1365V AC for 60 s, between field side

and system

No isolation between individual channels

System throughput (8

channels scanned) – Add

0.5 ms if filtering is

selected

Typical module timing is shown here.

7.4 ms - millivolt

8.0 ms -

Ω

- 2-wire RTD

10.0 ms -

Ω

- 3-wire RTD

10.4 ms -

Ω

- 4-wire RTD

8.0 ms - 2-wire RTD (°F)

10.4 ms - 4-wire RTD (°F)

8.8 ms - 2-wire RTD (°C), (°K)

10.8 ms - 4-wire RTD (°C), (°K)

9.8 ms - 3-wire RTD (°F)

10.0 ms - 3-wire RTD (°C), (°K)

9.0 ms - Thermocouples (°F)

9.4 ms - Thermocouples (°C), (°K)

Open circuit protection

RTD mode – Open input – Module defaults to max value

TC mode – Open input – Module defaults to min value

To simulate wire-off detection in Series A TC mode when using

a Series B module, attach a jumper from terminal 39 to terminal

48 on the 1794-TB3G, 1794-TB3GS, or 1794-TB3GK terminal

base unit so that an open input will default to max value.

Open input detection time

Immediate detection 2 scans, max

Overvoltage capability

15V DC continuous at 25 °C

Overall drift with

temperature, max

50 ppm/°C of span

Cold junction

compensation range

-20…100 °C

Cold junction compensator Allen-Bradley catalog number 1794-CJC2
Indicators

1 green power status indicator

8 red open input indicators

FlexBus current

40 mA

Power dissipation, max

3.0 W @ 31.2V DC

Thermal dissipation, max

10.2 BTU/hr @ 31.2V DC

Keyswitch position

3

External DC power

supply voltage

Voltage range

Supply current

24V DC nom

95 mA @ 24V DC

Dimensions (with module

installed in base) HxWxD

approx.

94 x 94 x 69 mm

(3.7 x 3.7 x 2.7 in.)

Temperature code, IEC

T4

General Specifications

Attribute

Value