Publication 1794-6.5.12 - September 2011

Calibrate Your Module 47

2. Apply power to the module for 20 minutes before calibrating.

3. After the connections stabilize, initiate a write word with the appropriate

EDT command location (write word 3, bits 00…15) as shown above.

4. Monitor the value in the EDT response location (read word 11,

bits 00…15) for an echo of the EDT command. Depending on which
command you sent, it should show 242X Hex.

If the EDT response word reads 80FF (hex), repeat step 3. Make sure to
allow for sufficient time for the module to respond to your request. If
there is no change, calibration has failed. Check the wiring and try again.

5. Set the precision millivolt source to the value required for a gain of 2.

Repeat steps 3 and 4 for gain 2. Repeat for each gain setting.

When all gain calibrations are successful, proceed to perform Current Source
Calibration
on page 47.

Current Source Calibration

The current sources can be calibrated one at a time or all at once. To calibrate
all the current sources, proceed as follows:

1. Connect a 383

Ω

, 0.01% resistor across (H, +) and (L, -) of each input

channel (8 resistors).

2. Apply power to the module for 20 minutes before calibrating.

EDT Commands for Gain Calibration

All Channels

Single Channel

EDT Command

EDT
Command
Dec. or Hex
Bits 8

15

EDT Command
Data
Dec. or Hex

Gain
Selected

Input (mV)

Hex

Decimal

Bits
4

7

Bits
0

3

1

-320.00 + 0.064 mV

2420

9248

06

0

7

0

2

320.00 + 0.032 mV

2421

9249

06

0

7

1

4

110 + 0.016 mV

2422

9250

06

0

7

2

8

70.00 + 0.008 mV

2423

9251

06

0

7

3

16

29.00 + 0.004 mV

2424

9252

06

0

7

4

32

19.00 + 0.002 mV

2425

9253

06

0

7

5