Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 47

Advertising
background image

Publication 1794-6.5.12 - September 2011

Read and Write Configuration Maps for the FLEX I/O Module 35

Write Word 0

(continued)

Bits 08…11

(10…13)

Bit

11 10 09 08

Data type for channels 0…7

0

0

0

0

°C (implied decimal point xxxx.x)

0

0

0

1

°F (implied decimal point xxxx.x)

0

0

1

0

°K (implied decimal point xxxx.x)

0

0

1

1

-32767…+32767

0

1

0

0

0…65535

0101…1111 not used

Bits 12…15

(14…17)

Not used

Write Word 1

Bits 00…03

Sensor Type (Thermocouple or RTD)

RTD Type
Bit

03 02 01 00

Sensor type for channels 0…3

0

0

0

0

Resistance (default)

0

0

0

1

100

Ω

Pt

α

= 0.00385 Euro (-200…+870 °C) (-328…1598 °F)

0

0

1

0

200

Ω

Pt

α

= 0.00385 Euro (-200…+400 °C) (-328…752 °F)

0

0

1

1

100

Ω

Pt

α

= 0.003916 U.S. (-200…+630 °C) (-328…1166 °F)

0

1

0

0

200

Ω

Pt

α

= 0.003916 U.S. (-200…+400 °C) (-328…752 °F)

0

1

0

1

100

Ω

Nickel (-60…+250 °C) (-76…482 °F)

0

1

1

0

200

Ω

Nickel (-60…+200 °C) (-76…392 °F)

0

1

1

1

120

Ω

Nickel (-80…+320 °C) °F) (-112…608 °F)

1

0

0

0

10

Ω

Copper (-200…+260 °C) °F) (-328…500 °F)

1001…1111 not used

Thermocouple Type
Bit

03 02 01 00

Sensor type for channels 0…3

0

0

0

0

mV (default)

0

0

0

1

B 300…1800 °C (572…3272 °F)

0

0

1

0

E -270…1000 °C (-454…1832 °F)

0

0

1

1

J -210…1200 °C (-346…2192 °F)

0

1

0

0

K -270…1372 °C (-454…2502 °F)

0

1

0

1

TXK/XK(L) -200…800 °C (-328…1472 °F)

0

1

1

0

N -270…1300 °C (-450…2372 °F)

0

1

1

1

R -50…1768 °C (-58…3214 °F)

1

0

0

0

S -50…1768 °C (-58…3214 °F)

1

0

0

1

T -270…400 °C (-454…752 °F)

1010…1111 not used

Bits 04…05

Sensor Mode Select bits
Bit

05 04 Sensor mode select for channels 0…3

Thermocouple

Bit/Word Descriptions for Block Transfer Write Words

Word

Dec. Bits
(Octal Bits)

Description

Advertising