North american hazardous location approval – Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 78

Advertising
background image

Publication 1794-6.5.12 - September 2011

66

Safety Approvals

North American Hazardous
Location Approval

The 1794-IRT8, 1794-IRT8K, and 1794-IRT8XT modules are North
American Hazardous Location approved.

The following information applies when operating
this equipment in hazardous locations.

Informations sur l’utilisation de cet équipement en
environnements dangereux.

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for

use in Class I Division 2 Groups A, B, C, D, hazardous

locations and nonhazardous locations only. Each product is

supplied with markings on the rating nameplate indicating

the hazardous location temperature code. When combining

products within a system, the most adverse temperature

code (lowest “T” number) may be used to help determine the

overall temperature code of the system. Combinations of

equipment in your system are subject to investigation by the

local Authority Having Jurisdiction at the time of

installation.

Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne

conviennent qu’à une utilisation en environnements de Classe

I Division 2 Groupes A, B, C, D dangereux et non dangereux.

Chaque produit est livré avec des marquages sur sa plaque

d’identification qui indiquent le code de température pour les

environnements dangereux. Lorsque plusieurs produits sont

combinés dans un système, le code de température le plus

défavorable (code de température le plus faible) peut être

utilisé pour déterminer le code de température global du

système. Les combinaisons d’équipements dans le système

sont sujettes à inspection par les autorités locales qualifiées

au moment de l’installation.

EXPLOSION HAZARD

•Do not disconnect equipment unless

power has been removed or the area is

known to be nonhazardous.

•Do not disconnect connections to this

equipment unless power has been

removed or the area is known to be

nonhazardous. Secure any external

connections that mate to this

equipment by using screws, sliding

latches, threaded connectors, or other

means provided with this product.

•Substitution of components may

impair suitability for Class I, Division 2.

•If this product contains batteries, they

must only be changed in an area

known to be nonhazardous.

•Couper le courant ou s’assurer que

l’environnement est classé non

dangereux avant de débrancher

l'équipement.

•Couper le courant ou s'assurer que

l’environnement est classé non

dangereux avant de débrancher les

connecteurs. Fixer tous lesconnecteurs

externes reliés à cet équipement à

l'aide de vis, loquets coulissants,

connecteurs filetés ou autres moyens

fournis avec ce produit.

•La substitution de composants peut

rendre cet équipement inadapté à une

utilisation en environnement de Classe

I, Division 2.

•S’assurer que l’environnement est

classé non dangereux avant de changer

les piles.

WARNING

AVERTISSEMENT

Advertising