Configure Your FLEX I/O Module with RSLogix 5000 Software 25

7. After you have completed all the Module Configuration parameters,

click OK in the Module Properties dialog box.

Sensor Mode

Allows you to select the operational mode for the

thermocouple or RTD inputs. For thermocouple inputs,

you can choose the cold junction compensation mode.

For RTD inputs, you can choose 2-wire, 2-wire with

user selected RTD offset, 3-wire, and 4-wire.

Default for thermocouples is external compensation;

default for RTDs is 2-wire (with no offsets).

For Thermocouple

External compensation

Internal compensation

No compensation

Differential compensation

For a description of the

different sensor mode

options, for both

Thermocouple and RTD,

see Bit/Word

Descriptions for Block

Transfer Write Words,

on page 34.

For RTD

2-wire compensation (default)

2-wire with Loop compensation

3-wire

4-wire

When you select

Internal Compensation

for your Thermocouple,

you need to specify a

corresponding

Reference Junction

value. This parameter

sets a fixed reference

junction to compensate

all thermocouple

channels and ranges

from 0 °C…70 °C.

When you select 2-wire

with Loop compensation

for your RTD, you need

to specify values for

each channel for the

RTD Loop

Compensation.

Input Filter Cutoff Allows you to select one of eight levels on input

filtering. The single pole, low pass filtering is

accomplished by the module microprocessor. The filter

selections range from Hardware Only to 5 s time

constant. The times are approximate because they are

based on the module scan time, which varies. The

default is Hardware Only.

Hardware Filter Only (default)

25 ms

100 ms

250 ms

500 ms

1 s

2 s

5 s

Data Format

Allows you to specify the format of the data reported.

Module defaults to -4000…10000 in millivolt mode,

and 0…5000 in

Ω

mode with implied decimal points

(i.e. -40.00mV, 0.1

Ω

) whenever °C, °F, °K is selected.

°C

°F

°K

-32767…32767

0…65535

Configuration Parameters