Publication 1794-6.5.12 - September 2011

38

Read and Write Configuration Maps for the FLEX I/O Module

Using Series A
Functionality in a
Series B Module

To employ Series A functionality when using a Series B 1794-IRT8 module,
connect a wire from terminal 39 to terminal 48 on the 1794-TB3G or
1794-TB3GS terminal base unit. When terminals 39 and 48 are wired together,
bit 4 in read word 9 will not be set (0), indicating the module is in Series A
functionality.

Chapter Summary

This chapter provided the user with data and instructions to configure and
map data for the FLEX I/O Thermocouple, RTD, and Millivolt Input
module.

Write Word 3

00…07

Extended data table data bits

– These bits are written to the module during calibration. They are

used to define offset, gain and general channel calibration.

08…14

(10…16)

Extended data table command bits

– These bits are written to the module during calibration. They

are used to select channel calibration action.

15 (17)

Reserved for factory use only

Bit/Word Descriptions for Block Transfer Write Words

Word

Dec. Bits
(Octal Bits)

Description

ATTENTION

If these terminals are not connected together, the Series B

product will default to Series B functionality.