Publication 1794-6.5.12 - September 2011

Calibrate Your Module 45

Offset Calibration

Inputs can be calibrated one at a time or all at once. To calibrate the offsets,
proceed as follows:

1. Apply power to the module for 20 minutes before calibrating.

2. Connect a precision millivolt source across each input channel. Set the

source to -320.00 mV for a gain of 1. Connect all (L) signal terminals
together and attach to the positive lead from the precision voltage
source. Connect all (-) signal terminals together and attach to the
negative lead.

1

1

gain = 2, input = 0.0 mV

1

2

gain = 4, input = -50 mV

1

3

gain = 8, input = -10.0 mV

1

4

gain = 16, input = -9 mV

1

5

gain = 32, input = 1.0 mV

Gain calibration all

channels

2

0

gain = 1, input = 320 mV

2

gain = 2, input = 320 mV

2

gain = 4, input = 110 mV

2

gain = 8, input = 70 mV

2

gain = 16, input = 29 mV

2

gain = 32, input = 19 mV

Config Word 3
EDT Command
bits 8…15

Meaning

Config Word 3
bits 4…7

Config Word 3
bits 0…3

Meaning

EDT Commands for Offset Calibration

All Channels

Single Channel

EDT Command

EDT
Command
Dec. or Hex
Bits 8

15

EDT Command
Data
Dec. or Hex

Gain
Selected

Input (mV)

Hex

Decimal

Bits
4

7

Bits
0

3

1

-320.00 + 0.064 mV 2410

9232

05

0

7

0

2

0.000 + 0.032 mV

2411

9233

05

0

7

1

4

-50.00 + 0.016 mV

2412

9234

05

0

7

2