Publication 1794-6.5.12 - September 2011

34

Read and Write Configuration Maps for the FLEX I/O Module

Word

Dec. Bits
(Octal Bits)

Description

Read Word 10

00…07

Extended data table data response bits

– These

bits echo the EDT command data written to the

module during calibration.

08…14

(10…16)

Extended data table command response bits

These bits echo the EDT command written to the

module during calibration.

15 (17)

Reserved for factory use

Bit/Word Descriptions for Block Transfer Write Words

Word

Dec. Bits
(Octal Bits)

Description

Write Word 0

00…02

Input Filter Selection bits
Bit

02 01 00 Filter Time Constants – actual filtering depends on the module mode of

operation

0

0

0

Hardware filtering only (default filtering)

0

0

1

25 ms

0

1

0

100 ms

0

1

1

250 ms

1

0

0

500 ms

1

0

1

1s

1

1

0

2

s

1

1

1

5

s

Bits 03…05

Reference Junction

– used when input type is set to thermocouple and sensor mode is set to

internal compensation. Sets a fixed reference junction to compensate all thermocouple channels.
Bit

05 04 03 Reference Junction
0

0

0

0 °C (32 °F)

0

0

1

20 °C (68 °F)

0

1

0

25 °C (77 °F)

0

1

1

30 °C (86 °F)

1

0

0

40 °C (104 °F)

1

0

1

50 °C (122 °F)

1

1

0

60 °C (140 °F)

1

1

1

70 °C (158 °F)

Bits 06…07

Fault Mode bits

– when a bit is set (1), fault mode is enabled for that channel. Bit 06 corresponds to

channels 0…3; bit 07 corresponds to channels 4…7.

0 = Disabled

1 = Enable wire-off detection

Bits 08…11

(10…13)

Data format

– module defaults to -4000…10000 in millivolt mode, and 0…5000 in

Ω

mode with

implied decimal points (i.e. -40.00mV, 0.1

Ω

) whenever °C, °F, °K is selected.